Backflow assembly test: 5097 Quarry Dr
ApprovedFiled Sep 6, 2023 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 6, 2023
- Assembly type
- RP
- Serial number
- K597343
- Size
- 1
- Test gauge serial
- G-2791
- Gauge calibration date
- Nov 23, 2022
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-34-01234
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.