Backflow assembly test: 1823 Mill Creek Trl

Approved

Filed May 26, 2025 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
May 26, 2025
Assembly type
RP
Serial number
B660222
Size
3/4
Test gauge serial
G-3771
Gauge calibration date
Jan 11, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-32-01214
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1823 Mill Creek Trl
Owner: Jordan Danner
Parcel 093-32-01214