Backflow assembly test: 5178 Fox Run Ct

Approved

Filed Apr 11, 2026 by Emerson Calloway, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Apr 11, 2026
Assembly type
RP
Serial number
B374792
Size
3/4
Test gauge serial
G-1925
Gauge calibration date
Jul 5, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 093-19-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.