Backflow assembly test: 4781 Fox Run Way

Approved

Filed Aug 25, 2025 by Reese Hollins, Lakeside Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 25, 2025
Assembly type
RP
Serial number
Z946884
Size
1
Test gauge serial
G-7716
Gauge calibration date
Dec 14, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Hollins, current on the service date
  • All required fields present
  • Address matches parcel 093-22-01079
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.