Back to the backflow review queue
Backflow assembly test: 9498 Mill Creek Trl
ApprovedFiled Nov 26, 2025 by Cameron Nguyen, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 26, 2025
- Assembly type
- RP
- Serial number
- K625274
- Size
- 3/4
- Test gauge serial
- G-3257
- Gauge calibration date
- Nov 12, 2024
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Nguyen, current on the service date
- All required fields present
- Address matches parcel 085-40-01037
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9498 Mill Creek Trl
Owner: Drew Harlow
Parcel 085-40-01037