Back to the backflow review queue

Backflow assembly test: Riverside Market

Approved

Filed Sep 11, 2026 by Cameron Nguyen, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Sep 11, 2026
Assembly type
DC
Serial number
B312494
Size
1 1/2
Test gauge serial
G-1266
Gauge calibration date
Mar 9, 2026
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-25-01280
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2488 Laurel Trl
Owner: Danner Holdings LLC
Parcel 085-25-01280