Back to the backflow review queue
Backflow assembly test: 6358 Mill Creek Ct
Sent backFiled Nov 23, 2026 by Jordan Nguyen, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- RP
- Serial number
- B519392
- Size
- 3/4
- Test gauge serial
- G-6744
- Gauge calibration date
- Sep 25, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Nguyen, current on the service date
- All required fields present
- Address matches parcel 085-39-01052
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
6358 Mill Creek Ct
Owner: Rowan Danner
Parcel 085-39-01052