Backflow assembly test: 7904 Stone Gate Way
ApprovedFiled Sep 17, 2026 by Hayden Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 17, 2026
- Assembly type
- RP
- Serial number
- A751082
- Size
- 3/4
- Test gauge serial
- G-1887
- Gauge calibration date
- Jan 13, 2026
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Lindqvist, current on the service date
- All required fields present
- Address matches parcel 085-17-01311
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7904 Stone Gate Way
Owner: Avery Marsh
Parcel 085-17-01311