Back to the backflow review queue

Backflow assembly test: Golden Animal Hospital

Approved

Filed Mar 23, 2024 by Hayden Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 23, 2024
Assembly type
RP
Serial number
K800193
Size
1
Test gauge serial
G-4471
Gauge calibration date
May 28, 2023
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 085-32-01326
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4954 Meadow Lark Rd
Owner: Ellery Holdings LLC
Parcel 085-32-01326