Backflow assembly test: 1385 Turkey Hill Ct

Approved

Filed Oct 24, 2025 by Hayden Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 24, 2025
Assembly type
PVB
Serial number
B342605
Size
1
Test gauge serial
G-1637
Gauge calibration date
Apr 27, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 085-86-01181
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1385 Turkey Hill Ct
Owner: Drew Whitcomb
Parcel 085-86-01181