Back to the backflow review queue

Backflow assembly test: Main Street Animal Hospital

Approved

Filed Mar 13, 2024 by Hayden Danner, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 13, 2024
Assembly type
RP
Serial number
Z235664
Size
1
Test gauge serial
G-1161
Gauge calibration date
Aug 24, 2023
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 085-10-01312
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4085 Mill Creek Dr
Owner: Harlow Holdings LLC
Parcel 085-10-01312