Back to the backflow review queue

Backflow assembly test: Two Rivers Apartments

Approved

Filed Nov 6, 2026 by Logan Danner, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 6, 2026
Assembly type
RP
Serial number
W300730
Size
2
Test gauge serial
G-9455
Gauge calibration date
Apr 15, 2026
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Danner, current on the service date
  • All required fields present
  • Address matches parcel 085-37-01197
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4672 Fox Run Dr
Owner: Ramirez Holdings LLC
Parcel 085-37-01197