Backflow assembly test: Crossroads Animal Hospital

Approved

Filed Jun 25, 2024 by Hayden Lindqvist, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 25, 2024
Assembly type
RP
Serial number
B151725
Size
2
Test gauge serial
G-8704
Gauge calibration date
May 7, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 085-61-01027
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.