Backflow assembly test: Crossroads Pizza
ApprovedFiled Nov 8, 2025 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 8, 2025
- Assembly type
- RP
- Serial number
- K634526
- Size
- 4
- Test gauge serial
- G-7154
- Gauge calibration date
- Jun 4, 2025
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Ellery, current on the service date
- All required fields present
- Address matches parcel 083-17-01250
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
7464 Turkey Hill Way
Owner: Stroud Holdings LLC
Parcel 083-17-01250