Back to the backflow review queue

Backflow assembly test: 561 Fox Run Rd

Approved

Filed May 2, 2024 by Casey Ellery, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 2, 2024
Assembly type
RP
Serial number
B188292
Size
3/4
Test gauge serial
G-4042
Gauge calibration date
Jul 27, 2023
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-37-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

561 Fox Run Rd
Owner: Emerson Ramirez
Parcel 083-37-01073