Backflow assembly test: Corner Taqueria

Approved

Filed Feb 18, 2025 by Reese Ashby, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Feb 18, 2025
Assembly type
RP
Serial number
B788854
Size
4
Test gauge serial
G-8131
Gauge calibration date
Oct 9, 2024
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
1.8 psid
Relief valve opened at
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ashby, current on the service date
  • All required fields present
  • Address matches parcel 083-62-01352
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2858 Spring Branch Rd
Owner: Lindqvist Holdings LLC
Parcel 083-62-01352