Backflow assembly test: 4963 Mill Creek Dr

Approved

Filed Oct 18, 2024 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 18, 2024
Assembly type
PVB
Serial number
K942289
Size
3/4
Test gauge serial
G-3633
Gauge calibration date
Aug 26, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-27-01252
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4963 Mill Creek Dr
Owner: Hayden Kessler
Parcel 083-27-01252