Backflow assembly test: Main Street Grill

Approved

Filed Jan 2, 2026 by Reese Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 2, 2026
Assembly type
DC
Serial number
A990333
Size
1
Test gauge serial
G-9780
Gauge calibration date
Jun 24, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Kessler, current on the service date
  • All required fields present
  • Address matches parcel 083-36-01060
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6446 Ridgeview Dr
Owner: Marsh Holdings LLC
Parcel 083-36-01060