Backflow assembly test: 3395 Meadow Lark Ln

Approved

Filed Jun 25, 2025 by Jordan Fairley, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 25, 2025
Assembly type
RP
Serial number
B424144
Size
1
Test gauge serial
G-6691
Gauge calibration date
May 14, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Fairley, current on the service date
  • All required fields present
  • Address matches parcel 083-80-01124
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.