Backflow assembly test: 278 Quarry Trl

Approved

Filed Mar 15, 2026 by Reese Ashby, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Mar 15, 2026
Assembly type
RP
Serial number
Z823078
Size
3/4
Test gauge serial
G-4796
Gauge calibration date
Aug 12, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ashby, current on the service date
  • All required fields present
  • Address matches parcel 083-41-01045
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.