Back to the backflow review queue
Backflow assembly test: 9530 Old Church Rd
ApprovedFiled Jun 28, 2024 by Jordan Fairley, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 28, 2024
- Assembly type
- PVB
- Serial number
- K450942
- Size
- 1
- Test gauge serial
- G-5904
- Gauge calibration date
- May 29, 2024
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Fairley, current on the service date
- All required fields present
- Address matches parcel 083-79-01066
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9530 Old Church Rd
Owner: Blake Ramirez
Parcel 083-79-01066