Backflow assembly test: Maple Leaf Brewing Co

Approved

Filed Jul 22, 2025 by Casey Hollins, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 22, 2025
Assembly type
DC
Serial number
W436457
Size
1
Test gauge serial
G-4020
Gauge calibration date
Jan 26, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Hollins, current on the service date
  • All required fields present
  • Address matches parcel 083-93-01231
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5875 Old Church Trl
Owner: Okafor Holdings LLC
Parcel 083-93-01231