Back to the backflow review queue

Backflow assembly test: 1808 Spring Branch Ln

Approved

Filed Apr 16, 2026 by Casey Hollins, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 16, 2026
Assembly type
RP
Serial number
B867715
Size
3/4
Test gauge serial
G-2610
Gauge calibration date
Jun 4, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Hollins, current on the service date
  • All required fields present
  • Address matches parcel 083-53-01022
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1808 Spring Branch Ln
Owner: Riley Pruitt
Parcel 083-53-01022