Backflow assembly test: 193 Fox Run Trl

Approved

Filed Nov 8, 2025 by Parker Okafor, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 8, 2025
Assembly type
DC
Serial number
W499498
Size
3/4
Test gauge serial
G-4307
Gauge calibration date
Mar 3, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-75-01037
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.