Back to the backflow review queue
Backflow assembly test: Golden Grill
ApprovedFiled Oct 28, 2026 by Sam Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 28, 2026
- Assembly type
- RP
- Serial number
- A417983
- Size
- 1 1/2
- Test gauge serial
- G-9463
- Gauge calibration date
- Sep 10, 2026
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-29-01303
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6578 Pine Knoll Rd
Owner: Okafor Holdings LLC
Parcel 079-29-01303