Backflow assembly test: Golden Grill

Approved

Filed Oct 28, 2026 by Sam Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 28, 2026
Assembly type
RP
Serial number
A417983
Size
1 1/2
Test gauge serial
G-9463
Gauge calibration date
Sep 10, 2026
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-29-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6578 Pine Knoll Rd
Owner: Okafor Holdings LLC
Parcel 079-29-01303