Back to the backflow review queue

Backflow assembly test: Golden Grill

Approved

Filed Oct 8, 2025 by Parker Okafor, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 8, 2025
Assembly type
RP
Serial number
A417983
Size
1 1/2
Test gauge serial
G-8623
Gauge calibration date
Apr 14, 2025
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-29-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6578 Pine Knoll Rd
Owner: Okafor Holdings LLC
Parcel 079-29-01303