Backflow assembly test: Station Diner

Approved

Filed Sep 15, 2023 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 15, 2023
Assembly type
DC
Serial number
K366101
Size
4
Test gauge serial
G-3134
Gauge calibration date
Feb 6, 2023
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-10-01181
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3407 Hickory Trl
Owner: Hollins Holdings LLC
Parcel 079-10-01181