Back to the backflow review queue

Backflow assembly test: 5850 Old Church Rd

Approved

Filed Nov 4, 2026 by Sam Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Nov 4, 2026
Assembly type
DC
Serial number
A805128
Size
3/4
Test gauge serial
G-7852
Gauge calibration date
Aug 27, 2026
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-74-01309
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5850 Old Church Rd
Owner: Riley Lindqvist
Parcel 079-74-01309