Backflow assembly test: Maple Leaf Diner

Approved

Filed Aug 6, 2024 by Sam Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Aug 6, 2024
Assembly type
RP
Serial number
Z771893
Size
1 1/2
Test gauge serial
G-6196
Gauge calibration date
Apr 27, 2024
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-17-01208
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.