Backflow assembly test: Riverside Pizza
ApprovedFiled Aug 14, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 14, 2026
- Assembly type
- RP
- Serial number
- W243056
- Size
- 4
- Test gauge serial
- G-4407
- Gauge calibration date
- May 26, 2026
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-87-01082
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.