Backflow assembly test: 6255 Laurel Rd
ApprovedFiled Mar 9, 2025 by Sam Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 9, 2025
- Assembly type
- RP
- Serial number
- W198420
- Size
- 3/4
- Test gauge serial
- G-3237
- Gauge calibration date
- Jan 1, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-90-01063
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6255 Laurel Rd
Owner: Logan Whitcomb
Parcel 079-90-01063