Backflow assembly test: 481 Spring Branch Dr

Approved

Filed Aug 29, 2026 by Parker Okafor, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 29, 2026
Assembly type
DC
Serial number
W978634
Size
3/4
Test gauge serial
G-9727
Gauge calibration date
Jul 24, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
3.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-97-01191
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

481 Spring Branch Dr
Owner: Morgan Harlow
Parcel 079-97-01191