Backflow assembly test: 8219 Orchard Dr
ApprovedFiled Nov 17, 2025 by Sam Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 17, 2025
- Assembly type
- RP
- Serial number
- K127540
- Size
- 1
- Test gauge serial
- G-6329
- Gauge calibration date
- Mar 5, 2025
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-67-01039
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8219 Orchard Dr
Owner: Quinn Stroud
Parcel 079-67-01039