Back to the backflow review queue
Backflow assembly test: 9181 Mill Creek Rd
ApprovedFiled Aug 13, 2024 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 13, 2024
- Assembly type
- DC
- Serial number
- W688032
- Size
- 1
- Test gauge serial
- G-9568
- Gauge calibration date
- Apr 20, 2024
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 079-93-01049
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9181 Mill Creek Rd
Owner: Morgan Pruitt
Parcel 079-93-01049