Back to the backflow review queue

Backflow assembly test: 441 Sycamore Way

Approved

Filed Dec 10, 2025 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 10, 2025
Assembly type
RP
Serial number
K222300
Size
1
Test gauge serial
G-6444
Gauge calibration date
Oct 28, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-14-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

441 Sycamore Way
Owner: Drew Vance
Parcel 079-14-01147