Backflow assembly test: 441 Sycamore Way

Approved

Filed Oct 5, 2023 by Parker Nguyen, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 5, 2023
Assembly type
RP
Serial number
K222300
Size
1
Test gauge serial
G-6916
Gauge calibration date
Jul 9, 2023
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
3.4 psid
Relief valve opened at
3.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 079-14-01147
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

441 Sycamore Way
Owner: Drew Vance
Parcel 079-14-01147