Backflow assembly test: Crossroads Grill

Approved

Filed Jun 25, 2025 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 25, 2025
Assembly type
RP
Serial number
K756640
Size
2
Test gauge serial
G-2733
Gauge calibration date
Jul 20, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-10-01112
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.