Back to the backflow review queue
Backflow assembly test: Corner Market
Needs reviewFiled Nov 20, 2026 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 20, 2026
- Assembly type
- RP
- Serial number
- W871311
- Size
- 4
- Test gauge serial
- G-7031
- Gauge calibration date
- Feb 25, 2026
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 079-61-01279
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
8463 Hickory Dr
Owner: Pruitt Holdings LLC
Parcel 079-61-01279