Backflow assembly test: 4152 Pine Knoll Rd
ApprovedFiled Aug 15, 2026 by Parker Nguyen, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 15, 2026
- Assembly type
- RP
- Serial number
- K700801
- Size
- 3/4
- Test gauge serial
- G-9647
- Gauge calibration date
- Mar 3, 2026
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 079-74-01306
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4152 Pine Knoll Rd
Owner: Hayden Brandt
Parcel 079-74-01306