Backflow assembly test: 5907 Turkey Hill Trl

Approved

Filed Apr 21, 2023 by Parker Okafor, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 21, 2023
Assembly type
PVB
Serial number
B889877
Size
1
Test gauge serial
G-6120
Gauge calibration date
Jan 2, 2023
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-60-01035
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.