Back to the backflow review queue

Backflow assembly test: 1132 Orchard Rd

Approved

Filed May 11, 2026 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 11, 2026
Assembly type
PVB
Serial number
Z660047
Size
3/4
Test gauge serial
G-2615
Gauge calibration date
Dec 30, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-18-01201
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1132 Orchard Rd
Owner: Hayden Nguyen
Parcel 079-18-01201