Backflow assembly test: 7262 Pine Knoll Dr

Approved

Filed Aug 10, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Aug 10, 2025
Assembly type
DC
Serial number
K325686
Size
1
Test gauge serial
G-7247
Gauge calibration date
May 30, 2024
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
1.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-42-01184
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.