Back to the backflow review queue

Backflow assembly test: 1396 Orchard Dr

Approved

Filed Jun 1, 2026 by Casey Lindqvist, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 1, 2026
Assembly type
RP
Serial number
B300276
Size
1
Test gauge serial
G-8792
Gauge calibration date
Mar 6, 2026
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.1 psid
Relief valve opened at
2.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 077-17-01261
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1396 Orchard Dr
Owner: Logan Whitcomb
Parcel 077-17-01261