Back to the backflow review queue

Backflow assembly test: 925 Meadow Lark Way

Approved

Filed Nov 15, 2026 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 15, 2026
Assembly type
RP
Serial number
B305288
Size
3/4
Test gauge serial
G-2415
Gauge calibration date
Jul 10, 2026
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-17-01114
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

925 Meadow Lark Way
Owner: Morgan Calloway
Parcel 077-17-01114