Backflow assembly test: 5297 Sycamore Rd

Approved

Filed May 30, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
May 30, 2025
Assembly type
RP
Serial number
W552728
Size
3/4
Test gauge serial
G-2437
Gauge calibration date
Feb 14, 2025
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-41-01324
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5297 Sycamore Rd
Owner: Cameron Harlow
Parcel 077-41-01324