Back to the backflow review queue
Backflow assembly test: 4886 Mill Creek Rd
ApprovedFiled May 13, 2026 by Casey Lindqvist, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 13, 2026
- Assembly type
- RP
- Serial number
- K770624
- Size
- 1
- Test gauge serial
- G-3118
- Gauge calibration date
- Dec 23, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Lindqvist, current on the service date
- All required fields present
- Address matches parcel 077-50-01285
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4886 Mill Creek Rd
Owner: Taylor Kessler
Parcel 077-50-01285