Back to the backflow review queue

Backflow assembly test: 9362 Quarry Ct

Approved

Filed Oct 18, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 18, 2025
Assembly type
DC
Serial number
Z955795
Size
3/4
Test gauge serial
G-3880
Gauge calibration date
Sep 2, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-91-01168
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9362 Quarry Ct
Owner: Hayden Hollins
Parcel 077-91-01168