Backflow assembly test: 4886 Mill Creek Rd
ApprovedFiled Jun 2, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 2, 2025
- Assembly type
- RP
- Serial number
- K770624
- Size
- 1
- Test gauge serial
- G-1114
- Gauge calibration date
- Mar 10, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Hollins, current on the service date
- All required fields present
- Address matches parcel 077-50-01285
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4886 Mill Creek Rd
Owner: Taylor Kessler
Parcel 077-50-01285