Back to the backflow review queue

Backflow assembly test: 4848 Pine Knoll Dr

Approved

Filed Aug 16, 2025 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 16, 2025
Assembly type
RP
Serial number
B273604
Size
1
Test gauge serial
G-7734
Gauge calibration date
May 23, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-19-01203
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4848 Pine Knoll Dr
Owner: Parker Ellery
Parcel 077-19-01203