Backflow assembly test: Riverside Grill

Approved

Filed Mar 3, 2026 by Casey Lindqvist, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 3, 2026
Assembly type
RP
Serial number
K391570
Size
4
Test gauge serial
G-7129
Gauge calibration date
Jun 17, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
1.9 psid
Relief valve opened at
3.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 077-15-01101
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5192 Pine Knoll Way
Owner: Ashby Holdings LLC
Parcel 077-15-01101